Limits and Energy Consumption of Adiabatic Microclimate Control in Textile Shops Under the Climatic Conditions of Bukhara
Issue:
Volume 15, Issue 6, December 2026
Pages:
160-174
Received:
4 November 2026
Accepted:
12 November 2026
Published:
25 November 2026
Abstract: In textile spinning and weaving shops, air temperature and relative humidity are process parameters. In a hot dry climate, adiabatic humidification of outdoor air in a spray chamber is energetically attractive, but its capability is limited by the outdoor air state. This study quantifies the limits of maintaining the indoor state of a textile shop adiabatically in the climate of Bukhara (Uzbekistan) and the air, water and electricity required. The heat and moisture balances were written jointly in enthalpy form, expressing the outdoor air fraction, the humidification load and the applicability condition of the adiabatic method through the indoor–outdoor enthalpy difference. Monthly Bukhara weather station data for 2021–2025 and a diurnal temperature model were used; the study is a model-based assessment not yet validated by measurements in an operating shop. For an indoor state of 26°C and 60%, the enthalpy difference is 48.8 kJ/kg in January and 7.7 kJ/kg in July and approaches zero during the hot hours of July days. At the design airflow, the indoor state cannot be maintained adiabatically for 522 hours per year for the multi-year mean climate (489–706 hours in the individual years 2021–2024), and for another 306 hours this would require a spray chamber efficiency above 0.85. Humidification consumes 0.68 kg of water in January and 2.32 kg in July per 1 kWh of process electricity. The supply fan power equals 18.5% of the process power, and the fans account for 90–95% of the estimated annual operating cost of 1.9–2.0 million UZS (158–166 USD) per 1 kW of process power. A summer indoor state of 28°C and 60% eliminates the restricted hours completely. A chiller operating only in the restricted hours would consume 64–102 kWh per 1 kW of process power per year, about one-eighth of the chiller electricity of a conventional system with a fixed outdoor air fraction, whereas the adiabatic system uses about three times more water in the warm season. The restricted hours depend mainly on the indoor design state and the outdoor humidity ratio. The results can support the design and the choice of the summer operating mode of air conditioning systems in textile enterprises in hot dry climates.
Abstract: In textile spinning and weaving shops, air temperature and relative humidity are process parameters. In a hot dry climate, adiabatic humidification of outdoor air in a spray chamber is energetically attractive, but its capability is limited by the outdoor air state. This study quantifies the limits of maintaining the indoor state of a textile shop ...
Show More